FIST-GPS Generic Patch and Splicing Shelves
FIST-GPS shelves feature the FIST fibre management system and provide a platform for patching and splicing within a rack environment. The shelves house FIST splice and patch trays (FIST-GPST-12 or FIST-GPSTF-12). They mount in ETSI (FIST-GR3), 19- or 15-inch (FIST-GR3F) racks.
Trays with adapter/retainers; trays are staggered for easy fibre routing and access to connectors, and are provided in sets of two trays.
FIST-GPS3 shelves feature FIST-GPST 15-inch trays without retainers; trays can be stacked directly on each other. FIST-GPS3 shelves are used in 15-inch frames
Features
- Patching, using patch cords, connectorised breakout or intrafacility cables
- Splicing loose tube cables, non-connectorised intrafacility or breakout cables to pigtails and patching these pigtails to patch cords
- Supports integration of passive optical splitters and wavelength division multiplexers
- Various connector/adapter types possible
- Optional jumper over-length storage facility (for 19-inch shelves)
- Full patching capability on the tray and between trays in one shelf
- Use of connectorised cables allows repair of pigtails
- Easy identification of each fibre
- Available with various capacities and in different heights (44, 89, 125 and 175mm; please note, 44mm height is available only for 19-inch shelves)
- Kits available to attach cables at the side or back of shelf
- Wrap-around side panel and pigtail guide for easy re-patching (except in 44mm versions)
- Can be installed in CommScope’s FIST racks and other 19-inch or metric (ETSI) rack sizes
— FIST-GPS2 mount in ETSI and 19-inch frames
— FIST-GPS3 mount in 15-inch frames - Shelves are shipped with the maximum number of trays already installed.
Benefits of Tray Patching
- Clean: Both sides easily accessible for cleaning adapters
- Safe: Laser light oriented perpendicularly to the operator
- Accessible: Full front access at both sides of connection
- Visible: Patch cords do not hamper access or visibility of ports
- Reconnection to other positions in the same tray or shelf does not result in uncontrolled over-lengths
- Bend controls guide and protect the pigtail cable and ensure controlled cable routing
- Manipulation of patch cords does not cause transient losses on other circuits
- Secure: Because of their position in the trays, connectors are better protected than in some front facing patch shelves
- Shelves are painted (powder-coated) in light grey (RAL 7035)
- Shelves are always ordered fully loaded.
- FIST-GPS2 shelves feature trays with adapters and retainers
- FIST-GPS3 shelves feature trays with adapters without retainers
- For a list of accessories, consumables and tools, please refer to the GPS2/3 accessories ordering guide
Dimensions and Capacities
FIST-GPS2
19”/ETSI rack mounting; mounting brackets for both mounting environments included in kit

FIST-GPS3
15” rack mounting

GPS2/3 Standard Kit Content
- Metal chassis with drawer
- Mounting brackets (ETSI/19” included)
- Drawer includes:
— Bracket onto which trays can be mounted
— 2 tray support wedges
— Hook and loop strap to secure the trays
— Bend control(s) at the patching side for some configurations - Splice/patch versions include foam and tie-wraps to fix the cable elements (loose tubes, break-out cable, intra-facility subunits) onto the trays
- Trays which include:
— Splice protector holder (SMOUV or ANT)
— Splice protectors (only if SMOUV option is selected) - One or two trumpets for guiding pigtails as they exit the shelf
- Metal front cover:
— 175 mm high version: hingeable and removable cover
— 125 mm high version: hingeable and removable cover
— 89 mm high version: hingeable, fixed cover (GPS2); hingeable, removable cover (GPS3)
— 44 mm high version: front cover is part of the drawer, not hingeable - Identification cards and card holders (not for GPS2-L-version)
- Mounting screws and nuts
- Installation Instructions
FIST-GPS2: 19” and ETSI Rack Mounting
Patch only. No cable. FIST-GPST-12 trays

Items to be ordered separately:
- Pigtails, patch cords, break-out and IFC (OCI, OCJ, OCIP)
- Group termination unit if non-connectorised breakout cable is to be used (FIST-GTU2)
FIST-GPS2: 19” and ETSI Rack Mounting
Splice/Patch. No cable. FIST-GPST-12 trays
Splice/Patch. No cable. FIST-GPST-12 trays

Items to be ordered separately:
- Fusion splice protectors (according to type of tray chosen)
- Pigtails, patch cords, breakout and IFC (OCI, OCJ, OCIP)
- Group termination unit if non-connectorised breakout cable is to be used (FIST-GTU2)
For use in 19” or ETSI shelves
FIST-GPST-12 trays used in FIST-GPS2 shelves are asymmetrical; the patching area is not located in the centre of the tray but moved slightly to one side.
The patching areas of 2 consecutive trays should not fall on each other but alter. In general, all the patch cords of the trays within one shelf should leave the shelf at the same side.
-These trays use adapters with retainers.
-Trays are supplied in sets of two complementary pieces.
Standard kit content
- Patch/patch configuration: tray with 2 patch units
- Splice/patch configuration:
— 1 patch and 1 splice unit
— Splice protector holder (SMOUV or ANT)
— Splice protectors (if SMOUV option is selected)
— Adapters, 900μ pigtails as per options selected - GTU2 (group termination units for non-connectorised breakout cable applications) are ordered separately
Dimensions and Capacities
FIST-GPST-12 (19-inch)
Ordering Information
1 Patch cords or cables leave shelf to right; patch field to left of tray
2 Patch cords or cables leave shelf to left; patch field to right of tray
3 45 mm SMOUV heat shrink splice protector
4 ANT splice holder ONLY; splice protectors must be ordered separately
Trays for 19-inch Splice/Patch Shelves only with IFC (without strength member)
Dimensions and Capacities
FIST-GPST-12 (19-inch)
Ordering Information
FIST-GPS3: 15” Rack Mounting
Patch only. No cable. FIST-GPSTF-12 trays

Items to be ordered separately:
- Pigtails, patch cords, break-out and IFC (OCI, OCJ, OCIP)
- Group termination unit if non-connectorised breakout cable is to be used (FIST-GTU2)
FIST-GPS3: 15” Rack Mounting
Splice/Patch. No cable. FIST-GPSTF-12 trays

2 Patch field to left of tray; patch cords or cables leave shelf to right
3 Patch field to right of tray; patch cords or cables leave shelf to left
4 45 mm SMOUV heat shrink splice protector
5 ANT splice holder ONLY; splice protectors must be ordered separately
Items to be ordered separately:
- Fusion splice protectors (according to type of tray chosen)
- Pigtails, patch cords, breakout and IFC (OCI, OCJ, OCIP)
- Group termination unit if non-connectorised breakout cable is to be used (FIST-GTU2)
Trays for 15-inch Splice/Patch and Patch/Patch Shelves: No Cable
FIST-GPSTF-12 (15-inch)
Ordering Information

1 Patch cords or cables leave shelf to right; patch field to left of tray
2 Patch cords or cables leave shelf to left; patch field to right of tray
3 45 mm SMOUV heat shrink splice protector
4 ANT splice holder ONLY; splice protectors must be ordered separately
Trays for 15-inch Splice/Patch Shelves only: with IFC or OSP Cable
FIST-GPSTF-12 (15-inch)
Ordering Information